Like our Room Alert 32S, this model is packed with the most capacity for the most sensors. It monitors temperature, humidity and its own main-vs-battery-power status. With room for 30 sensors/accessories each and the capacity to toggle multiple low-voltage electrical devices, it’s got your environment covered.
When conditions exceed your thresholds, Room Alert notifies you right away so you can act quickly.
Send email and text messages right from the device.
Trigger the warning LEDs and siren sound on a Light Tower.
Pair with RoomAlert.com (or other compatible platforms) for even more alerting capabilities.
Looking for support for secure protocols like HTTPS, SSL, TLS and SNMP v3? Consider the Room Alert 32S.
Like the Room Alert 32S, this unit is packed with the most sensing capacity: it monitors your facility for temperature and humidity and boasts a generous capacity for up to 26 more sensors. Our standard Room Alert 32E package includes 1 external Digital Active Power Sensor w/ Temperature to help monitor the power status of critical electronic devices that draw 100W of power or more. 4 additional ports allow you to toggle low-voltage electrical devices, such as an AC units, fans, alarm panels and the warning LEDs/siren sound on a Light Tower.
This feature-packed model houses an internal battery backup that can supply up to 15 minutes of power to the device. Should main power falter, that extra uptime allows the unit to execute critical notifications and actions. A dedicated internal power sensor watches the battery back up, letting you know if the device is on main or battery power.
The Room Alert 32E fits 1U of rack space in a server cabinet, but can also hang from a ceiling or on a wall from its rotating rack wings. Perfect for areas requiring comprehensive coverage, this unit is at home in data centers, warehouses and any space requiring eyes on a wide variety of conditions—or on the same condition in multiple targeted locations.
Related
Video
Related
Technical Specification
This list applies to both RA32S and RA32E Models
Room Alert 32E Specifications
Feature
Description
Internal Temperature Sensor
Condition Monitored
Indoor ambient temperature
Type
Digital
Range
-40 to 185 F (-40 to 85 C)
Accuracy
+/- 2° C
Resolution
0.03125° C
Reading
Numeric values in Fahrenheit or Celsius
Internal Humidity Sensor
Condition Monitored
Indoor relative humidity (RH), non-condensing
Type
Digital
Range
5% – 85% RH
Accuracy
+/- 4.5% RH at 5 to 59% RH
+/- 6.5% RH at 60 to 95% RH
Resolution
0.333% RH
Reading
Numeric values in % RH
Internal Power Sensor
Condition Monitored
Power status of the Room Alert 32S
Type
Switch
Range
Open/Closed
Reading
“Battery power”/”Main power”
External sensor & accessory ports
8 digital sensor ports (RJ-11)
16 switch sensor ports (screw terminal blocks)
2 Light Tower & Relay Adapter ports (RJ-11)
2 relay output ports (screw terminal blocks)
2 analog sensor ports (screw terminal blocks)
Power & connectivity ports
1 5V barrel-connector power jack 1 RJ-45 Ethernet port (PoE-enabled)
Power supply
AVTECH 5V power adapter (100/240 VAC, 50/60 Hz, RoHS) or PoE (IEEE802.3af compliant)